Fluke 2 In 1 Insulation Multimeter, 1587-FC
Key features
- Safety first. Connect the insulation tester then keep yourself out of harm's way by monitoring your test measurements remotely.
- Prove your job is done right by quickly seeing and sharing insulation resistance test results wirelessly with your smartphone.
- Quickly find problems by saving and comparing measurements over time on a wireless device.
DATASHEET
Hurry Up! Sold: 100/0 products in stock.
General Specifications | ||
Maximum voltage applied to any terminal and common | 1000 V | |
Storage temperature | -40 °C to 60 °C (-40 °F to 140 °F) | |
Operating temperature | -20 °C to 55 °C (-4 °F to 131 °F) | |
Temperature coefficient | 0.05 x (specified accuracy) per °C for temperatures <18 °C or >28 °C (<64 °F or >82 °F) | |
Relative humidity | Noncondensing | |
0% to 95% @ 10 °C to 30 °C (50 °F to 86 °F) | ||
0% to 75% @ 30 °C to 40 °C (86 °F to 104 °F) | ||
0% to 40% @ 40 °C to 55 °C (104 °F to 131 °F) | ||
Vibration | Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument | |
Radio frequency communication | 2.4 GHz ISM Band | |
Radio frequency certification | FCC: T68-FBLE, IC: 6627A-FBLE | |
Electromagnetic Compatibility | ||
International | IEC 61326-1:Portable Electromagnetic Environment; IEC 61326-2-2 CISPR 11: Group 1, Class A | |
Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself. | ||
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances. | ||
Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object. The equipment may not meet the immunity requirements of this standard when test leads and/or test probes are connected. | ||
Korea (KCC) | Class A Equipment (Industrial Broadcasting & Communication Equipment) | |
Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes. | ||
USA (FCC) | 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103. | |
Enclosure protection | IEC 60529: IP40 (non-operating) | |
Safety | ||
IEC 61010-1 | Pollution Degree 2 | |
IEC 61010-2-033 | CAT IV 600 V / CAT III 1000 V | |
Batteries | Four AA batteries (IEC LR6) | |
Battery life | Meter use 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. | |
Size (H x W x L) | 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in) | |
Weight | 550 g (1.2 lb) | |
Altitude | Operating | 2000 m |
Storage | 12,000 m | |
Over-range capability | 110% of range except for capacitance which is 100% | |
Frequency overload protection | <107 V Hz | |
Fuse protection for mA input | 0.44A, 1000 V, IR 10 kA |